Free Joint Preliminary Status Report - District Court of Federal Claims - federal


File Size: 1,015.8 kB
Pages: 129
Date: May 31, 2006
File Format: PDF
State: federal
Category: District
Author: unknown
Word Count: 9,866 Words, 65,537 Characters
Page Size: Letter (8 1/2" x 11")
URL

https://www.findforms.com/pdf_files/cofc/20604/13-5.pdf

Download Joint Preliminary Status Report - District Court of Federal Claims ( 1,015.8 kB)


Preview Joint Preliminary Status Report - District Court of Federal Claims
Case 1:05-cv-01121-EJD
FY 2001 MCON PROJECT

Document 13-5

Filed 05/31/2006

Page 1 of 129
12003035

P-189, BUILDING 245 EXTENSION NPS, MONTEREY, CALIFORNIA

2.3.3

Fittings

Elbows, vaned elbows, take-offs, branch connections, transitions, splitters, volume dampers, fire dampers, flexible connections, and access doors shall conform with SMACNA DCS, Section 2. Provide factory fabricated airtight, and noncorrosive test holes with screw cap and gasket. 2.3.4 2.3.4.1 Acoustical Attenuator Systems Acoustical Duct Lining

Flexible or rigid mineral fiber lining conforming to ASTM C 1071. Lining shall not be less than one inch thick. 2.3.4.2 Net Noise Reduction Values

Conform with the following: Minimum Net Noise Reduction Values, Sound Pressure Level dB (Reference Sound Power at 10-12 Watts) Octave Pass Band Center-Frequency (Hz) Noise Reduction (dB) 2.3.4.3 2 125 11 3 250 16 4 500 19 5 1000 30 6 2000 40 7 4000 32

Sound Attenuators (Traps)

Provide factory-fabricated attenuators constructed of galvanized steel sheets. Outer casing shall be not less than 22 gage. Acoustical fills shall be mineral fiber conforming to ASTM C 1071. Air flow capacities shall be as indicated. Pressure drops through attenuators shall not exceed values indicated, or shall be not in excess of 15 percent of the total external static pressure of the air handling system, whichever is less. Acoustically test sound attenuators with metal duct inlet and outlet sections while under rated air flow conditions. Noise reduction data shall include effects of flanking paths and vibration transmission. Attenuators shall be airtight when operating at internal static pressure not less than 2 inches water gage. Conform with noise reduction requirements specified in paragraph entitled "Net Noise Reduction Values." 2.4 FLEXIBLE DUCTS AND CONNECTORS

UL 181, Class I, UL listed, SMACNA DCS, and additional requirements herein specified. Provide to connect between rigid ducts and outlets or terminals. There shall be no erosion, delamination, loose fibers, or odors from the ducts into the air stream. At 250 degrees F, minimum rating pressures shall be 2 inches water positive and 1/2 inch negative, up to 2500 fpm. Flexible ducts shall be maximum 6 feet in length. Minimum bend radius shall be twice the duct diameter. 2.4.1 Materials

Interlocking spiral or helically corrugated type constructed of non-collapsible fire-retardant, chloroprene or chlorosulphonated polyethylene impregnated, minimum 30 ounces per square yard woven mineral fabric.

SECTION 15810

Page 6

Case 1:05-cv-01121-EJD
FY 2001 MCON PROJECT

Document 13-5

Filed 05/31/2006

Page 2 of 129
12003035

P-189, BUILDING 245 EXTENSION NPS, MONTEREY, CALIFORNIA

2.4.2

Insulation and Vapor Barrier

ASTM C 553 Type 1, Class B-2, minimum one inch nominal thickness and three-quarter lb./cu. ft.density. Sheathe insulation with a vapor barrier having a maximum water vapor permeance of 0.20 perm in accordance with ASTM E 96, Procedure A. Coat ends of insulation with cement to prevent erosion and delamination. 2.4.3 Joints

Make airtight slip joints, seal with pressure-sensitive vapor-seal adhesive tape or duct sealer, and secure with sheet metal screws. To prevent insulation compression, place 2 inch wide by one inch thick closed cell foam plastic spacers over joints under vapor barriers. To provide a vaportight joint, provide a zinc-coated steel clamp over such spacers. 2.5 CASINGS AND PLENUMS

Factory fabricated components with field installation. Furnish certified testing data from plenum or casing manufacturer obtainable directly from an independent acoustical laboratory, listing sound absorption and transmission loss characteristics of panel assembly. Sound absorption coefficients and sound transmission loss, determined by an independent laboratory, shall be in accordance with ASTM C 423 and ASTM E 90 respectively. 2.6 2.6.1 DIFFUSERS, REGISTERS, AND GRILLES Material and Finishes

Provide factory-furnished diffusers, registers, and grilles constructed of steel. Exterior and exposed edges shall be rolled, or otherwise stiffened and rounded. Steel parts shall be factory zinc phosphate treated prior to priming and painting or have a baked-on enamel finish. Colors shall be selected or approved by Contracting Officer. 2.6.2 Sound Pressure Level

Manufacturer certified sound pressure level rating of inlets and outlets. Conform with the following permissible room sound pressure levels: NC 30 2.6.3 Throw Typical Application Any

The distance from the diffuser, register, or grille to the point which the air velocity falls below 50 feet per minute shall not exceed 1.5 times the outlet mounting height. 2.6.4 Drop

Maximum drop of air stream shall not be within 6 of the floor at the end of the throw. 2.6.5 Ceiling Diffusers

Equip with baffles or other devices required to provide proper air SECTION 15810 Page 7

Case 1:05-cv-01121-EJD
FY 2001 MCON PROJECT

Document 13-5

Filed 05/31/2006

Page 3 of 129
12003035

P-189, BUILDING 245 EXTENSION NPS, MONTEREY, CALIFORNIA

distribution pattern. Provide factory-fabricated, single key, volume dampers. Except for linear diffusers, internal parts shall be removable through the diffuser neck for access to the duct and without the use of special tools. 2.6.5.1 Circular, Square, and Rectangular Diffusers

Construct each ceiling diffuser of four or more concentric elements designed to deliver air in a generally horizontal direction without excess smudging of the ceiling. Interior elements of square and rectangular ceiling diffusers may be circular, square, or rectangular as manufacturer's standard. 2.6.5.2 Perforated Plate Diffusers

Provide adjustable air pattern controls as indicated. Diffuser faceplates shall not sag or deflect when operating under design conditions. 2.6.6 Registers

Double-deflection supply registers. Provide exhaust and return registers as specified for supply registers, except that exhaust and return registers shall have a single set of nondirectional face bars or vanes having the same appearance as the supply registers. 2.6.7 Grilles

Construct and finish as specified above for registers, except that volume dampers shall be omitted. 2.7 2.7.1 TROFFERS Air Seal

Resilient plastic self-adhering pressure sensitive seal between the diffuser and the frame of lighting fixtures. 2.7.2 Interior Dampers or Deflectors Finish

Black paint or anodized. 2.8 2.8.1 DUCT SLEEVES, PREPARED OPENINGS, AND CLOSURE COLLARS Duct Sleeves

Fabricate from minimum 20 gage galvanized steel. Where sleeves are installed in bearing walls, provide structural steel sleeves as indicated. Size sleeves to provide one inch clearance between duct and sleeve or between insulation and sleeve for insulated ducts. 2.8.2 Prepared Openings

Provide one inch clearance between the duct and the sleeve, or one inch clearance between insulation and sleeve for insulated ducts except at grilles, registers, and diffusers. 2.8.3 Packing

ASTM C 553, Type 1, Class B-2, mineral fiber. SECTION 15810 Page 8

Case 1:05-cv-01121-EJD
FY 2001 MCON PROJECT

Document 13-5

Filed 05/31/2006

Page 4 of 129
12003035

P-189, BUILDING 245 EXTENSION NPS, MONTEREY, CALIFORNIA

2.8.4

Closure Collars

Four inches wide minimum, fabricated from minimum 20 gage galvanized steel. 2.9 DEFLECTORS

Factory-fabricated and factory- or field-assembled units consisting of curved turning vanes for uniform air distribution and change of direction with minimum turbulence and pressure loss. Provide curved vanes for square elbows. For round ducts taking off from rectangular ducts, provide factory fabricated, galvanized sheet metal, spin-in fittings. These fittings shall have butterfly dampers and locking quadrant operators. 2.10 ACCESS DOORS

Door shall be rigid and airtight with neoprene gaskets and two or more galvanized steel hinges and quick fastening locking devices. Provide doors as large as practical. Mount doors, if possible, so that air pressure holds them closed. As an alternative, removable access doors may be used. These access doors shall be constructed from stamped sheet metal and consist of an inner and outer door panel. Where insulated doors are needed, the inner door shall consist of two panels spot-welded together which totally encapsulate fiberglass insulation. The inner and outer doors shall be joined by bolts and threaded handles in such a configuration that the panels can be drawn together to secure the door to the duct in a sandwich fashion. The handles shall be high impact plastic with threaded metal inserts. Conical springs shall be used between the door panels to facilitate installation and removal of the door. Neoprene gasket shall be used around the outside edge of the inner or outer panel, but not both, to seal the door. This type of door is approved for use on rectangular, round and flat-oval ductwork. 2.11 DAMPERS

Construct dampers and louvers with galvanized sheet metal two gages heavier than ducts in which installed. Except as modified herein, the construction shall be of aluminum or galvanized steel with interlocking edges and maximum 10 inch blade width. Conform with SMACNA DCS. Damper blades shall be connected to the damper frame with a non-metallic anti-friction bushing. The blades shall be connected to the frame with a galvanized, zinc coated steel anti-friction bearing pin. The pin shall consist of a single or double row sealed, stainless steel, maintenance free, roller or ball bearing, lubricated for life with a full stroke test of 200,000 or more strokes in accordance with UL 555S. The bearing shall be pressed onto a steel shaft via a knurled stud. A slotted dowel pin is then inserted thru a hole connecting the two pins. 2.11.1 Manual Volume Dampers

Balancing, factory-fabricated type. Equip dampers with accessible mechanism such as quadrant operators or 3/16 inch rods brought through the side of ducts with locking setscrew and bushing. Where quadrant operators are furnished, provide chrome plated or enamel painted type with exposed edges rounded. 2.11.2 Fire Dampers

Provide in accordance with UL 555. SECTION 15810 Page 9

Case 1:05-cv-01121-EJD
FY 2001 MCON PROJECT

Document 13-5

Filed 05/31/2006

Page 5 of 129
12003035

P-189, BUILDING 245 EXTENSION NPS, MONTEREY, CALIFORNIA

2.11.3

Automatic Smoke-Fire Dampers

Multiple blade type, 180 degrees F fusible fire damper link; smoke damper assembly to include electrically powered operator. UL 555 as a 1 1/2 hour rated fire damper; further qualified under UL 555S as a leakage rated damper. Leakage rating under UL 555S shall be no higher than Class II at an elevated temperature Category B (250 degrees F for 30 minutes). Pressure drop in the damper open position shall not exceed 0.1 inch w.g. with average duct velocities of 2500 fpm. 2.11.4 Bird Screens

ASTM E 437, general industrial-use wire cloth, Grade C, medium light or heavier, nominal 2 mesh 0.063 inch wire diameter, galvanized steel bird screens. Provide removable insect screens of grooved type, with vinyl or neoprene spline insert for securing screen cloth. PART 3 3.1 EXECUTION INSTALLATION

Conform to NFPA 90A, SMACNA DCS. Provide mounting and supporting of ductwork and accessories including, but not limited to, structural supports, hangers, vibration isolators, stands, clamps and brackets, access doors, and dampers. Provide electrical isolation between dissimilar metals. Electrical isolation may be fluorinated elastomers or sponge-rubber gaskets. Install ductwork accessories as indicated and as recommended by manufacturer's printed instruction. Allow clearance for inspection, repair, replacement, and service. Louvers in accordance with AMCA 501. 3.1.1 Ductwork

Air distribution systems shall operate with no chatter or vibration. 3.1.1.1 Field Changes to Ductwork

Those required to suit the sizes of factory-fabricated equipment actually furnished, shall be designed to minimize expansion and contraction. Use gradual transitions in field changes as well as modifications to connecting ducts. 3.1.1.2 Dampers

When installed on ducts to be thermally insulated, equip each damper operator with stand-off mounting brackets, bases, or adapters to provide clearance between the duct and operator not less than the thickness of insulation. Stand-off mounting items shall be integral with the operator or standard accessory of damper manufacturer. 3.1.1.3 Deflectors

Provide in square elbows, duct-mounted supply outlets, take-off or extension collars to supply outlets, and tap-in branch-off connections. Adjust supply outlets to provide air volume and distribution as specified. 3.1.1.4 Fire Dampers

SECTION 15810

Page 10

Case 1:05-cv-01121-EJD
FY 2001 MCON PROJECT

Document 13-5

Filed 05/31/2006

Page 6 of 129
12003035

P-189, BUILDING 245 EXTENSION NPS, MONTEREY, CALIFORNIA

Install in accordance with manufacturer's instructions for condition of UL 555 and NFPA 90A. Locate as indicated and provide surface penetration sleeves in accordance with approved detail drawings. 3.1.1.5 Access Doors

Provide for automatic dampers, volume dampers, fire dampers, coils, thermostats, temperature controllers, valves, filters, humidifiers and other concealed apparatus requiring service and inspection in the duct systems. 3.1.1.6 Duct Sleeves, Prepared Openings, and Closure Collars

Provide for ductwork penetrations in floors, walls, and partitions through which metallic ductwork passes. a. Duct Sleeves: Fill space between duct and sleeve or between insulation and sleeve for insulated ducts with mineral fiber, except at grilles, registers, and diffusers. Prepared Openings: Fill space between duct and opening or between insulation and opening for insulated ducts with mineral fiber, except at grilles, registers, and diffusers. Closure Collars: Fit collars snugly around ducts or insulation. Grind edges of collar smooth to preclude tearing or puncturing insulation covering or vapor barrier. Provide nails with maximum 6 inch centers on collars. Packing

b.

c.

3.1.1.7

Pack spaces between sleeve or opening and duct or duct insulation with mineral fiber. 3.1.2 Duct Hangers and Supports

SMACNA DCS, Section 4. Provide seismic restraint complying with SMACNA SRM. Attach supports only to structural framing members and concrete slabs. Do not anchor supports to metal decking unless a means is provided and approved for preventing the anchors from puncturing the metal decking. Where supports are required between structural framing member, provide suitable intermediate metal framing. Provide retainer clips where C clamps are used. 3.1.2.1 Flexible Ducts

Support ducts by hangers every 3 feet, unless supported by ceiling construction. Stretch flexible air ducts to smooth out corrugations and long radius elbows. Provide minimum length to make connections. 3.1.2.2 Flexible Connectors

Provide flexible connectors between fans and ducts or casings and where ducts are of dissimilar metals. For round ducts, securely fasten flexible connectors by zinc-coated steel clinch-type draw-bands. For rectangular ducts, lock flexible connectors to metal collars. 3.1.3 Inspection Plates and Test Holes

SECTION 15810

Page 11

Case 1:05-cv-01121-EJD
FY 2001 MCON PROJECT

Document 13-5

Filed 05/31/2006

Page 7 of 129
12003035

P-189, BUILDING 245 EXTENSION NPS, MONTEREY, CALIFORNIA

Provide, where required, in ductwork or casings for all balance measurements. If possible, test holes should be located at least 7.5 times diameters downstream from a disturbance. Extend cap through insulation. 3.1.4 Acoustical Duct Lining

SMACNA DCS, Section 2. Apply lining in cut-to-size pieces attached to interior of ducts with fire-resistant adhesive. Top and bottom pieces shall lap the side pieces. Secure pieces together with welded pins or clips. Do not distort ducts, burn through or mar the finish surface of ducts. Pins and washers shall be flush with the surface of duct liners. Seal breaks and punctures of duct-liner coating with fire-resistant adhesive. Coat exposed edges of the liner at duct ends and other joints where lining will be subject to erosion with a heavy brush coat of fire-resistant adhesive, to prevent delamination of glass fibers. 3.1.5 Sound Attenuators

Provide sound attenuators as indicated. For each system, provide sound attenuators to ensure that the combination of air system equipment and sound attenuation comply with the designed sound levels. 3.1.6 Flashing

Provide waterproof flashing where ducts pass through exterior walls and roofs. 3.1.7 Cleaning of Ducts

Remove all debris and dirt from ducts and wipe clean. Before installing air outlets, force air through entire system at maximum attainable velocity to remove accumulated dust. Provide temporary air filters to protect ductwork which may be harmed by excessive dirt. For large systems, clean duct with high power vacuum machines. 3.2 FIELD QUALITY CONTROL

Administer and direct tests. Furnish instruments, equipment, connecting devices, and personnel for the tests. Notify Contracting Officer 3 days before inspection or testing is scheduled. Correct defects in work. Repeat tests until work is in compliance. 3.2.1 Air Duct Leakage Tests

Perform duct air leakage test in accordance with Section 15950, "HVAC Testing/Adjusting/Balancing."

-- End of Section --

SECTION 15810

Page 12

Case 1:05-cv-01121-EJD
FY 2001 MCON PROJECT

Document 13-5

Filed 05/31/2006

Page 8 of 129
12003035

P-189, BUILDING 245 EXTENSION NPS, MONTEREY, CALIFORNIA

SECTION 15901

SPACE TEMPERATURE CONTROL SYSTEMS

PART 1 1.1

GENERAL REFERENCES

The Contractual Agreement, the Conditions of the Contract, and applicable portions of Division 1 and the Contract Drawings apply to the work of this Section as if printed herein. The publications are referred to in the text by the basic designations only. The sponsoring organizations of the publications are listed in Section 01420, "References." 1.2 RELATED REQUIREMENTS

Perform all work in this section in accordance with the paragraph entitled "Subcontractor Special Requirements" in Section 01310, "Administrative Requirements." 1.3 DEFINITION a. Year 2000 complaint - means computer controlled facility components that accurately process date and time data (including, but not limited to, calculating, comparing, and sequencing) from, into, and between the twentieth and twenty-first centuries, and the years 1999 and 2000 and leap year calculations.

1.4

SYSTEM DESCRIPTION

Provide new space temperature control systems complete and ready for operation. 1.5 SYSTEM REQUIREMENTS

Provide control systems composed of any combination of electric, analog electronic or pneumatic devices. Indicated control system devices of a particular type do not intend a requirement for the device unless the requirement is specifically indicated. Requirements apply to field installed control systems. 1.5.1 Centralized Direct Digital Control (DDC) Systems

A centralized DDC system shall be provided. Microprocessor-based single-loop controllers, unitary control system, variable-air-volume (VAV) boxes, and room thermostats may be used provided that the devices are manually configurable by the use of device firmware and require no software written by the Contractor for their application and use. 1.6 PERFORMANCE REQUIREMENTS

Provide control systems to maintain the required heating, ventilating, and cooling (HVAC) conditions by performing the functions and sequences of operations indicated. Control systems shall be complete, including all equipment and appurtenances, and ready for operation. Control systems SECTION 15901 Page 1

Case 1:05-cv-01121-EJD
FY 2001 MCON PROJECT

Document 13-5

Filed 05/31/2006

Page 9 of 129
12003035

P-189, BUILDING 245 EXTENSION NPS, MONTEREY, CALIFORNIA

shall be furnished, installed, tested, calibrated, and started up by, or under the supervision of trained technicians certified by the Contractor as qualified and regularly employed in such work. Control system equipment, valves, panels and dampers shall bear the manufacturer's nameplate. 1.7 1.7.1 DESIGN REQUIREMENTS Control System Diagrams

For each system, indicate HVAC process flow and location of devices relative to flow and to the HVAC control panel, the connections of control devices in control loops, references of control device contacts and device operating coils to line numbers of a ladder diagram and sequencing diagrams showing the operation of valves, dampers, and contacts relative to controller output, and HVAC process variables. 1.7.2 Ladder Diagram

Indicate connections and interlocks to control system devices and other devices such as starters, drives, HVAC control system panels, and HVAC equipment panels. Diagram shall be coordinated by line number and device number with each control system diagram. 1.7.3 Operating Parameters

Indicate operating parameters for devices shown on the control system diagram such as setpoints, ranges, limits, differentials, outside air temperature schedules, contact operating points, and HVAC equipment operating time schedules. 1.7.4 Automatic Control Valve Schedules

Indicate valve size, Cv, flow rate, pressure drop, top size, spring range, positioner range, operating signal characteristics, and power source. 1.7.5 Damper Schedules

Indicate damper sizes, quantities and sizes of actuators, spring ranges, positioner ranges, operating signal characteristics, and power source. 1.7.6 Wiring Diagram

Indicate terminal blocks, wire marker identification, connections to control system devices, external and internal power sources, and connections to external devices, starters, drives, control panels, jumpers, and ground connections. 1.7.7 Sequence of Operation

Sequence of operation for each HVAC control system coordinated with device identifiers on control system diagram and ladder diagram. 1.7.8 Arrangement Drawing

Arrangement diagram of each HVAC control system panel coordinated with device identifiers on the control system diagram and the ladder diagram. 1.8 SUBMITTALS

SECTION 15901

Page 2

Case 1:05-cv-01121-EJD
FY 2001 MCON PROJECT

Document 13-5

Filed 05/31/2006

Page 10 of 129
12003035

P-189, BUILDING 245 EXTENSION NPS, MONTEREY, CALIFORNIA

Submit the following in accordance with Section 01332, "Submittals During Construction for Design Build." SD-02 Shop Drawings Control system diagrams for each HVAC system; Ladder diagram; Operating parameters; Automatic control valve schedules; Damper schedules; Sequence of operation; Arrangement drawing; Wiring diagram; SD-03 Product Data Actuators; Valves; Dampers; Fire protection devices; Sensors; Thermostats; Sunshields; Pressure switches; Indicating devices; Controllers; Pressure gages; Control panels; VAV Terminal unit controls; SD-06 Test Reports Commissioning procedures; Calibration adjustment and commissioning reports; Site testing procedures identifying each item tested and describing each test.; Performance verification test plans and procedures; SECTION 15901 Page 3

Case 1:05-cv-01121-EJD
FY 2001 MCON PROJECT

Document 13-5

Filed 05/31/2006

Page 11 of 129
12003035

P-189, BUILDING 245 EXTENSION NPS, MONTEREY, CALIFORNIA

SD-07 Certificates Year 2000 (Y2K) Compliance Warranty; SD-10 Operation and Maintenance Data Space temperature control system, Data Package 3; G Submit operation and maintenance data in accordance with Section 01781, "Operation and Maintenance Data." SD-11 Closeout Submittals Air compressor; Refrigerated air dryer; Air filtration system; Training course documentation; Qualified service organization list; Certification of completion; 1.9 1.9.1 QUALITY ASSURANCE Standard Products a. Material and equipment shall be standard products of manufacturers regularly engaged in the manufacturing of such products, using similar materials, design and workmanship. The standard products shall have been in satisfactory commercial or industrial use for 2 years prior to bid opening. The 2-year use shall include applications of similarly sized equipment and materials used under similar circumstances. The 2 years experience must be satisfactorily completed by a product which has been sold or is offered for sale on the commercial market through advertisements, manufacturers' catalogs, or brochures. Products having less than a 2-year field service record will be acceptable if a certified record of satisfactory field operation, for not less than 6000 hours exclusive of the manufacturer's factory tests, can be shown. The equipment items shall be supported by a service organization.

b. 1.9.2

Nameplates and Tags a. Provide nameplates bearing legends as shown and tags bearing device unique identifiers as shown shall have engraved or stamped characters. Nameplates shall be mechanically attached to HVAC control panel doors. A plastic or metal tag shall be mechanically attached directly to each field-mounted device or attached by a metal chain or wire. Each airflow measurement station shall have a tag showing flow rate range for signal output range, duct size, and device identifier where shown. SECTION 15901 Page 4

b.

c.

Case 1:05-cv-01121-EJD
FY 2001 MCON PROJECT

Document 13-5

Filed 05/31/2006

Page 12 of 129
12003035

P-189, BUILDING 245 EXTENSION NPS, MONTEREY, CALIFORNIA

1.9.3

Verification of Dimensions

Contractor shall become familiar with details of work, shall verify dimensions in the field, and shall advise Contracting Officer of any discrepancy before performing work. 1.9.4 Modification of References

Accomplish work in accordance with ASME B31.1, ASME/ANSI B31.5, NFPA 70, and NFPA 90A, except as modified herein or indicated otherwise for equipment, materials, installation, examination, inspection, and testing. Consider the advisory or recommended provisions to be mandatory, as though the word "shall" had be substituted for the words "should" or "could" or "may," wherever they appear. Interpret reference to "authority having jurisdiction" and "owner" to mean the Contracting Officer. 1.9.5 Site Testing Procedures

Indicate test equipment to be used including manufacturers' names and model numbers, date of last calibration, and accuracy of calibration. 1.9.6 Commissioning Procedures

Define procedures specific to each control system including instructions on how to set control parameters and setpoints, proportional, integral and derivative mode constants, contact output settings, positioner range adjustments, and calibration checks of transmitters 1.9.7 Calibration Adjustment and Commissioning Reports

Submit specific to each HVAC control system, including settings adjustments and results of calibration checks 1.10 DELIVERY, STORAGE, AND HANDLING

Protect materials from the weather, humidity, and temperature variations, dirt and dust, and other contaminants, within the storage condition limits published by the equipment manufacturer. Store dampers so that seal integrity, blade alignment, and frame alignment are maintained. 1.10.1 Space Temperature Control System, Data Package 3

Submit Operation and Maintenance Manuals for items of equipment listed under paragraph entitled "Manufacturer's Catalog Data." Manual shall contain full hardware support documentation, which shall include but not be limited to the following: a. b. c. d. e. f. General description and specifications Installation and initial checkout procedures Detailed electrical and logical description Troubleshooting procedures, diagrams, and guidelines Alignment and calibration procedures for components Preventive maintenance requirements and a maintenance checklist SECTION 15901 Page 5

Case 1:05-cv-01121-EJD
FY 2001 MCON PROJECT

Document 13-5

Filed 05/31/2006

Page 13 of 129
12003035

P-189, BUILDING 245 EXTENSION NPS, MONTEREY, CALIFORNIA

g. h.

Detailed schematics and assembly drawings Spare parts list data, including required tool kits and suggested method of repairs such as field repair, factory repair, or item replacement Signal identification and timing diagrams Complete as-built control drawings, schedules, and sequence of operation Controller configuration and parameter setting procedures Step-by-step procedures required for each HVAC control systems startup, operation, shutdown, recovery, and fault diagnosis Manufacturer supplied operator manuals for equipment Qualified service organization list

i. j.

k. l.

m. n. 1.11 1.11.1

WARRANTY Year 2000 (Y2K) Compliance Warranty

For each product, component and system specified in this section as a "computer controlled facility component" provide a statement of Y2K compliance warranty for the specific equipment. The contractor warrants that each hardware, software, and firmware product delivered under this contract and listed below shall be able to accurately process date and time data (including, but not limited to, calculating, comparing, and sequencing) from, into, and between the twentieth and twenty-first centuries, and the years 1999 and 2000 and leap year calculations to the extent that other computer controlled components, used in combination with the computer controlled component being acquired, properly exchange data and time data with it. If the contract requires that specific listed products must perform as a system in accordance with the foregoing warranty, then that warranty shall apply to those listed products as a system. The duration of this warranty and the remedies available to the Government for breach of this warranty shall be defined in, and subject to, the terms and limitations of the contractor's standard commercial warranty or warranties contained in this contract, provided that, notwithstanding any provisions to the contrary, in such commercial warranty or warranties, the remedies available to the Government under this warranty shall include repair or replacement of any listed product whose non-compliance is discovered and made known to the contractor in writing within one year (365 days) after acceptance. Nothing in this warranty shall be construed to limit any rights or remedies the Government may otherwise have under this contract, with respect to defects other that Year 2000 performance. PART 2 2.1 PRODUCTS Y2K Compliant Products

Provide computer controlled facility components, specified in this section, that are Year 2000 compliant (Y2K). Computer controlled facility components refers to software driven technology and embedded microchip technology. This includes, but in not limited to, programmable thermostats, HVAC controllers, utility monitoring and control systems, SECTION 15901 Page 6

Case 1:05-cv-01121-EJD
FY 2001 MCON PROJECT

Document 13-5

Filed 05/31/2006

Page 14 of 129
12003035

P-189, BUILDING 245 EXTENSION NPS, MONTEREY, CALIFORNIA

alarms, and other facilities control systems utilizing microcomputer, minicomputer, or programmable logic controllers. 2.2 COMPONENTS

Provide components factory ordered for this project. Rebuilt equipment, warehoused equipment, or earlier generation equipment shall not be acceptable. Electrical, electronic, and electropneumatic devices not located within control panels shall have a NEMA 250 Type 1 enclosure in accordance with NEMA 250 unless otherwise specified. Actuators and positive positioners, and transmitters shall operate within temperature limit ratings of plus 35 to 150 degrees F. Panel mounted instruments shall operate within limit ratings of 35 to 120 degrees F and 10 percent to 95 percent relative humidity, non-condensing. Devices installed outdoors shall operate within limit ratings of minus 35 to 150 degrees F. 2.3 ACTUATORS

Provide electric, or electronic actuators. Actuators shall function as required within 85 to 110 percent of their power supply rating. Actuators shall fail to their spring return positions on signal or power failure unless indicated as timed, power return actuators. Actuators shall have visible position indicators. Where actuators do not have positive spring returns for fail-safe operation, provide capacity tanks, restrictors, check valves, and relays, or reserve power as required to achieve proper timed positioning for up to 4 minutes after primary power failure. Actuators shall open or close the devices to which they are applied within 60 seconds after a full scale signal input change. Pneumatic actuators shall be rated for 25 psig operating pressure except for high pressure cylinder type actuators. 2.3.1 Damper Actuators

Damper actuators shall be rated for at least 125 percent of the motive power necessary to operate the connected damper. The actuator stroke shall be limited by an adjustable stop in the direction of the return stroke. Actuators shall be provided with mounting and connecting hardware. 2.3.2 Valve Actuators

Valve actuators shall be rated for at least 125 percent of the motive power necessary to operate the valves over their full range of operation against the total and differential pressures. 2.4 AUTOMATIC CONTROL VALVES

Provide automatic control valves. 2.4.1 Valve Assembly

Valves shall have stainless steel stems and stuffing boxes with extended necks to clear the piping insulation. Valve bodies shall be designed for not less than 125 psig working pressure or 150 percent of the system operating pressure, whichever is greater. Maximum rated shutoff pressure of the valve shall exceed the rated deadhead pressure of the pump that supplies it. Valve leakage rating shall be 0.01 percent of rated Cv for soft-seated valves and 0.05 percent for metal-to-metal seated valves. Class 125 copper alloy valve bodies and Class 150 steel or stainless steel valves shall conform to ASME/ANSI B16.5 as a minimum. Components of cast SECTION 15901 Page 7

Case 1:05-cv-01121-EJD
FY 2001 MCON PROJECT

Document 13-5

Filed 05/31/2006

Page 15 of 129
12003035

P-189, BUILDING 245 EXTENSION NPS, MONTEREY, CALIFORNIA

iron valves shall conform to ASTM A 126 Class B or C as a minimum. 2.4.2 Two-Way Valves

Two-way modulating valves shall have equal percentage characteristics. 2.4.3 Three-Way Valves

Three-way valves shall provide constant total flow throughout full plug travel. 2.4.4 Duct-Coil and Convector/Fin-Tube Radiator Valves

Control valves with either flare-type or solder-type ends shall be provided for duct or terminal-unit coils. Flare nuts shall be provided for each flare-type end valve. 2.4.5 Valves for Chilled Water

ASME/ANSI B16.1. Bodies for valves 2 inches and smaller shall be brass or bronze, with threaded-end or union-end connections. Bodies for valves from 2.5 inches and larger shall be cast iron. Bodies for valves 2.5 inches and larger shall have flanged-end connections. Internal valve trim shall be brass or bronze except that valve stems may be Type 316 stainless steel. Water valves shall be sized for a 4 psi differential through the valve at rated flow, except as indicated otherwise. Select valve flow coefficient (Cv) for an actual pressure drop not less than 50 percent or greater than 125 percent of the design pressure drop at design flow. 2.4.6 Valves for Hot Water Service

Valves for hot water service below 250 Degrees F shall conform to ASME/ANSI B16.1. Bodies for valves 2 inches and smaller shall be brass or bronze, with threaded-end or union-end connections. Bodies for valves 2.5 inches and larger shall be cast iron. Bodies for 2.5 inches and larger shall have flanged-end connections. Water valves shall be sized for a 3 psi differential through the valve at rated flow, except as indicated otherwise. Select valve flow coefficient (Cv) for an actual pressure drop not less than 50 percent or greater than 125 percent of the design pressure drop at design flow. Internal trim, including seats, seat rings, modulating plugs, and springs, of valves controlling water hotter than 210 degrees F shall be Type 316 stainless steel. Internal trim for valves controlling water 210 degrees F or less shall be brass or bronze. Non-metallic parts of hot water control valves shall be suitable for a minimum continuous operating temperature of 250 degrees F or 50 degrees F above the system design temperature, whichever is higher. 2.4.7 Valves for Compressed Air Service

Valves used for switching compressed air supplied to pneumatic systems shall be brass body, three-way valves which shall conform to ANSI/ASME B16.15 Class 250. 2.5 DAMPERS

Provide dampers in air ducts. 2.5.1 Damper Assembly SECTION 15901 Page 8

Case 1:05-cv-01121-EJD
FY 2001 MCON PROJECT

Document 13-5

Filed 05/31/2006

Page 16 of 129
12003035

P-189, BUILDING 245 EXTENSION NPS, MONTEREY, CALIFORNIA

Damper shall conform to SMACNA DCS. A single damper section shall have blades no longer than 48 inches and shall be no higher than 72 inches. Maximum damper blade width shall be 8 inches. Larger sizes shall consist of a combination of sections. Dampers shall be steel or other materials where indicated. Flat blades shall be made rigid by folding the edges. Provide blades with compressible seals at points of contact. Provide channel frames of dampers with jamb seals to minimize air leakage. Dampers shall not leak in excess of 10 cfm per square foot at 4 inches water gage static pressure when closed. Seals shall be suitable for an operating temperature range of minus 40 degrees F to 200 degrees F. Dampers shall be rated at not less than 2000 fpm air velocity. Moving parts of the operating linkage in contact with each other shall consist of dissimilar materials. Damper axles shall be 0.5 inch minimum plated steel rods supported in the damper frame by stainless steel or bronze bearings. Blades mounted vertically shall be supported by a non-ferrous dissimilar thrust bearings. Pressure drop through dampers shall not exceed 0.05 inch water gage at 1,000 fpm in the wide-open position. Frames shall not be less than 2 inches wide. Dampers shall be tested in accordance with AMCA 500. 2.5.2 Operating Links

Operating links external to dampers, such as crank arms, connecting rods, and line shafting for transmitting motion from damper actuators to dampers, shall withstand a load equal to at least twice the maximum required damper-operating force. Rod lengths shall be adjustable. Links shall be brass, bronze, zinc-coated steel, or stainless steel. Mating parts shall consist of dissimilar materials. Working parts of joints and clevises shall be brass, bronze, or stainless steel. Adjustments of crank arms shall control the open and closed position of dampers. 2.6 FIRE PROTECTION DEVICES

Provide smoke detectors in return and supply air ducts on the downstream side of the filters in accordance with NFPA 90A, except as otherwise indicated. Provide UL listed or FM approved detectors for duct installation. 2.6.1 Smoke Detectors

Provide in systems having air-handling capacities over 2000 cfm in accordance with NFPA 90A. Furnish detectors under Section 13852, "Interior Fire Alarm System," and install under this section. 2.6.2 Combination Smoke/Fire Dampers

Dampers and actuator assemblies as required in accordance with NFPA 90A shall meet the Class II leakage requirements of UL 555S. Dampers shall be factory fabricated, galvanized steel or stainless steel with lubricated bearings, linkages, and seals to withstand temperatures from minus 20 to 250 degrees F. Provide replaceable seals. Combination smoke/fire dampers shall have a UL 1.5 hour rating and shall be equipped with electric/thermal links which close the damper at 165 degrees F and then automatically reset after normal temperature is restored by cycling damper actuator. Equip dampers with pneumatic or electric actuators which close smoke dampers tightly when activated. After the smoke has cleared, the dampers shall automatically reset.

SECTION 15901

Page 9

Case 1:05-cv-01121-EJD
FY 2001 MCON PROJECT

Document 13-5

Filed 05/31/2006

Page 17 of 129
12003035

P-189, BUILDING 245 EXTENSION NPS, MONTEREY, CALIFORNIA

2.7 2.7.1

SENSORS Spans and Ranges

Transmitters shall be calibrated to provide an electric or electronic output signal of 4 to 20 mA electric or electronic and 3 to 15 psi output for pneumatics over the indicated span or range. a. b. c. d. e. f. Conditioned space temperature, from 50 to 100 degrees F. Duct temperature, from 40 to 140 degrees F. Chilled water temperature, from 30 to 80 degrees F. Heating hot water temperature, from Outside air temperature, from minus 100 to 250 degrees F. 30 to 130 degrees F.

Differential pressure for VAV supply duct static pressure from 0 to 2.0 inches water gage.

2.7.2 2.7.2.1

Temperature Sensors Resistance Temperature Detectors (RTD's)

RTD shall be platinum with a tolerance of plus or minus 0.25 percent at 32 degrees F, and shall be encapsulated in epoxy, Series 300 stainless steel, anodized aluminum, or copper. RTD shall be furnished with RTD transmitter as specified, integrally-mounted unless otherwise indicated. 2.7.2.2 Continuous Averaging RTD's

Continuous averaging RTD's shall have a tolerance of plus or minus 1.0 degrees F at the reference temperature, and shall be of sufficient length to ensure that the resistance represents an average over the cross section in which it is installed. Sensing element shall have a bendable copper sheath. Averaging RTD shall be furnished with RTD transmitter as specified, to match the resistance range of the averaging RTD. Element length shall be a minimum of one linear foot per square foot of coil face area. 2.7.2.3 RTD Transmitter

RTD transmitter shall be selected to match the resistance range of the RTD. Transmitter shall be a two-wire, loop-powered device. Transmitter shall produce a linear 4 to 20 mA dc output corresponding to required temperature measurement. Output error shall not exceed 0.1 percent of the calibrated measurement. Transmitter shall include offset and span adjustments. 2.7.3 Pressure Sensors

Provide electronic pressure sensor and transmitter. Sensor shall be a pressure transmitter with an integral sensing element. Sensor over pressure rating shall be 25 psig above its normal operating range. Sensing element accuracy shall be plus or minus one percent of full scale. Transmitter accuracy shall be plus or minus 0.1 percent of the calibrated measurement. Transmitter shall be a two-wire, loop-powered device. Transmitter shall produce a linear 4 to 20 mA dc output corresponding to required pressure measurement. Transmitter shall have offset and span SECTION 15901 Page 10

Case 1:05-cv-01121-EJD
FY 2001 MCON PROJECT

Document 13-5

Filed 05/31/2006

Page 18 of 129
12003035

P-189, BUILDING 245 EXTENSION NPS, MONTEREY, CALIFORNIA

adjustments. 2.8 THERMOWELLS

Provide brass or Series 300 stainless steel thermowells with threaded brass plug and chain, 2 inch lagging neck and extension type well, and inside diameter and insertion length as required for the application. Provide thermowells for immersion sensors with conducting material inside the well. 2.9 THERMOSTATS

Provide thermostats. 2.9.1 Microprocessor-Based Room Thermostats

Microprocessor-based room thermostats shall have built-in keypads for scheduling of day and night temperature settings. When out of the scheduling mode, thermostats shall have continuous 12-hour time display, with AM and PM indication, continuous display of day of the week, and either continuous display of room temperature with display of temperature setpoint on demand, or continuous display of temperature setpoint with display of room temperature on demand. In the programmable mode, use the display for setting and interrogating time program ON-OFF setpoints for each day of the week. The time program shall allow two separate temperature setback intervals per day. Thermostats shall have a means for temporary and manual override of program schedule, with automatic program restoration on the following day. Thermostats shall have a replaceable battery to maintain timing and to maintain the schedule in memory for one year in the event of a power outage. Maximum differential shall be 2 degrees F. Where used for heat pump applications, thermostat shall have an emergency heat switch. 2.9.2 Low-Temperature Protection Thermostats (Freezestats)

Low-temperature protection thermostats shall be manually reset low-temperature safety thermostats, with NO and NC contacts or a two-position pneumatic output signal and a 20 foot element which shall respond to the coldest 18 inch segment. 2.10 SUNSHIELDS

Provide sunshields for outside air temperature sensing elements to prevent the sun from directly striking temperature sensing elements. Provide sunshields with adequate ventilation so that the sensing element responds to the ambient temperature of surroundings. The top of each sunshield shall have galvanized metal or aluminum rainshield projecting over the face of the sunshield. Sunshields shall be painted white or shall be unpainted aluminum. 2.11 PRESSURE SWITCHES AND SOLENOID VALVES

Provide pressure switches and solenoid valves. 2.11.1 Pressure Switches

Switches shall have an adjustable setpoint with visible setpoint scale. Range shall be as indicated. Differential adjustment shall span 20 to 40 percent of the range of the device.

SECTION 15901

Page 11

Case 1:05-cv-01121-EJD
FY 2001 MCON PROJECT

Document 13-5

Filed 05/31/2006

Page 19 of 129
12003035

P-189, BUILDING 245 EXTENSION NPS, MONTEREY, CALIFORNIA

2.11.2

Differential Pressure Switches

Switches shall be an adjustable diaphragm-operated device with two SPDT contacts, with taps for sensing lines to be connected to duct pressure fittings designed to sense air pressure. Fittings shall be angled-tip type with tips pointing into the airstream. 2.11.3 Pneumatic Electric (PE) Switches

Switches shall have an adjustable setpoint range of 3 to 20 psig. 2.11.4 Solenoid Operated Pneumatic (EP) Valves

Valves shall have three-port operation: common, normally open, and normally closed. Valves shall have an outer cast aluminum body. The connection shall be a 1/4 inch NPT threaded connection. Valves shall rated for 50 psig where used in a control system which operates at 25 or less, or 150 psig where used in a control system which operates in range of 25 to 100 psig. 2.12 INDICATING DEVICES

air be psig the

Provide indicating devices. 2.12.1 a. Thermometers Thermometers for insertion in ductwork and piping systems shall have brass, malleable iron, or aluminum alloy case and frame, clear protective face, and permanently stabilized glass tube with an indicating fluid column, white face, black numbers, and a 9 inch scale. Thermometers for piping systems shall have rigid stems with straight, angular, or inclined pattern. Thermometer stems shall have expansion heads as required to prevent breakage at extreme temperatures. On rigid stem thermometers, the space between bulb and stem shall be filled with a heat transfer medium. Air duct thermometers shall have perforated stem guards and 45 degree adjustable duct flanges with locking mechanisms. Averaging thermometers shall have 3.5 inch (nominal) dial, with black legend on white background, and pointer traveling through a 270 degree arc. Thermometers shall have an accuracy of plus or minus one percent of scale range. Thermometers shall have the following ranges: (1) Mixed air temperature: graduations. (2) Return air temperature: graduations. 0 to 100 degrees F in 1 degree F

b.

c.

d.

e.

f.

0 to 100 degrees F in 1 degree F

(3) Cooling coil discharge temperature: degree F graduations.

0 to 100 degrees F in 1

SECTION 15901

Page 12

Case 1:05-cv-01121-EJD
FY 2001 MCON PROJECT

Document 13-5

Filed 05/31/2006

Page 20 of 129
12003035

P-189, BUILDING 245 EXTENSION NPS, MONTEREY, CALIFORNIA

(4) Hydronic heating systems below 220 degrees F: degrees F in 2 degree graduations. (5) Chilled water temperature: graduations. 2.12.2 Pressure Gages

40 to 240

0 to 100 degrees F in one degree F

Provide pressure gages with gage cock, snubber, and syphon. a. ANSI/ASME B40.1. Gages shall be 2 1/2 inch (nominal) size, back-connected, suitable for field or panel mounting as required, shall have black legend on white background, and shall have a pointer traveling through a 270 degree arc. Accuracy shall be plus or minus 3 percent of scale range. Gages for indicating signal output to pneumatic actuators and main air gages shall have scale of 0 to 30 psig in 1 psig graduations. Gages for air storage tanks and for use before and after dirt and oil filters or dryers, shall have a scale of 0 to 160 psig with 2 psig graduations. Gages for hydronic system applications shall have ranges and graduations as indicated. Pneumatic transmission receiver gages shall have a range to match the respective transmitters.

b.

c.

d.

e.

2.13

LOW-DIFFERENTIAL PRESSURE GAGES

Gages for low-differential pressure measurements shall be 4 1/2 inch (nominal) size with two seats of pressure taps, and shall have a diaphragm-actuated pointer, white dial with black figures, and pointer zero adjustment. Gages shall have ranges and graduations as indicated. Accuracy shall be plus or minus 2 percent of scale range. 2.14 2.14.1 2.14.1.1 CONTROLLERS Single-Loop Controllers Controller Features

Controller shall be a microprocessor-based, single-loop device that does not require Contractor-generated software. Controller shall conform to FCC Part 15. Controller panel cutout shall be 3.62 by 3.62 inches. Controller shall have field selectable range for process variables, a remote setpoint analog input and analog output with adjustable high and low end limits, and proportional control manual reset adjustment. Analog output shall result from PID control. Analog output shall be configurable as direct acting and reverse acting. Controller shall have keyboard, display, auto/manual selection for control of analog output, and remote setpoint adjustment/local setpoint adjustment selection. Controller shall have adjustable high-end and low-end limits, ratio, and bias adjustments on remote setpoint input; operator initiated self-tune/manual-tune selection, anti-reset wind-up feature, and two configurable independent SPDT with adjustable system contact closure outputs. Controller shall be configurable to power-up in manual with local setpoint control, in automatic with local setpoint control, and in automatic with remote SECTION 15901 Page 13

Case 1:05-cv-01121-EJD
FY 2001 MCON PROJECT

Document 13-5

Filed 05/31/2006

Page 21 of 129
12003035

P-189, BUILDING 245 EXTENSION NPS, MONTEREY, CALIFORNIA

setpoint control. Contact closures shall be activated by a process variable and by a process variable deviation from setpoint as configured. The range of hysteresis adjustment shall not be smaller than 1 percent to 5 percent of process variable input span. Controller shall power the analog output loop to 20 mA where connected to a load of 600 ohms. Controller shall have 5-year battery backup or shall have nonvolatile memory to store operating parameters. 2.14.1.2 Controller Parameter Input and Display

Control parameters shall be entered and displayed directly, in the correct engineering units, through a series of keystrokes on a front panel display with a 3 1/2-digit, seven-segment display, with decimal point and polarity indication. Use of the display shall allow manual interrogation of setpoint, mode constants, and values of process variables and outputs. 2.14.1.3 Controller Electrical Requirements

Controller shall be powered by 120 Vac. Controller shall provide electrical noise isolation, not less than 100 dB at 60 Hz common mode rejection ratio, and not less than 60 dB at 60 Hz normal mode rejection ratio between ac power line and process variable input, remote setpoint input, and output signals. 2.14.1.4 Controller Accuracy

Controller shall have an accuracy of plus or minus 0.30 percent of input span, plus or minus one digit. 2.14.1.5 Controller Self Tuning

Controller self-tuning operation shall apply proportional, integral, and derivative modes of control; mode constants shall be modified as required. Self tuning shall only operate when selected from the front panel. 2.14.1.6 Controller Manual Tuning

Controller manual tuning operation shall provide proportional, integral, and derivative control modes, or any combination thereof, by means of individual mode constant adjustments. Adjustments shall be set for the appropriate value if a particular control mode action is desired, or to zero for the particular mode not desired. The proportional mode constant shall be adjustable from 0 to 200 percent of input signal range; the integral mode constant shall be adjustable from 0 to 20 repetitions per minute; and the derivative mode constant shall be adjustable from 0 to 5 minutes. 2.15 CONTROL DEVICES AND ACCESSORIES

Provide control devices and accessories. 2.15.1 Function Modules

Function modules shall accept mA dc analog input signals to produce analog output signals or contact output signals. Modules shall have zero and span adjustments for analog outputs, and setpoint adjustments for contact outputs. 2.15.1.1 Minimum Position Switches and Temperature Setpoint Devices SECTION 15901 Page 14

Case 1:05-cv-01121-EJD
FY 2001 MCON PROJECT

Document 13-5

Filed 05/31/2006

Page 22 of 129
12003035

P-189, BUILDING 245 EXTENSION NPS, MONTEREY, CALIFORNIA

Minimum position switches and temperature setpoint devices shall accept manual input and shall produce steady analog output. Switches and devices shall be suitable for recessed wall mounting or panel mounting and shall have a graduated dial. 2.15.1.2 Signal Inverter Modules

Signal inverter modules shall accept analog input signal and produce analog output signal that linearly reverses the direction of signal change of input versus output. 2.15.1.3 High-Low Signal Selector Modules

High-low signal selector modules shall accept analog input signals and select either the highest or the lowest input signal as the output signal. 2.15.1.4 Sequencer Modules

Sequencer modules shall provide fixed time delayed sequencing of one or more contact transfers from an analog input signal. Sequencers shall return contacts to their zero input signal condition when power is interrupted. 2.15.2 Relays

Relays shall be two-pole, double-throw (DPDT) with a 10-ampere resistive rating at 120 Vac, and shall have an enclosed coil. Provide with a light indicator which is lit when the coil is energized and is not lit when the coil is not energized. 2.15.3 Time-Delay Relays The

Time-delay relays shall be DPDT with octal connectors and dust covers. adjustable timing range shall be 0 to 3 minutes. 2.15.4 Time Clocks

Time clocks shall be a 24-hour, 365-day programmable timing device with two independently timed circuits. Clocks shall have a manual scheduling keypad and alphanumeric display of timing parameters. Timing parameters shall include Gregorian calendar date for month, day and day-of-month indication; and 24-hour time-of-day display, with one-minute resolution for programming the ON and OFF times for each circuit. Circuits shall have programmable timed override from 1 to 99 minutes. Clocks shall have capacity for programming four ON events and four OFF events for each circuit. Programmed events shall be assignable to a 365-day schedule. Clocks shall have automatic standard time and daylight saving time adjustments, keyed to input of appropriate dates. Provide clocks with 4-day battery backup. 2.15.5 Override Timer

Override timers shall be manually set, mechanically driven timers, or electronic timers, without a "hold" feature. Time intervals shall be selectable for up to 12 hours of operation and shall expire unless reset. 2.15.6 Regulated Power Supplies

Power supplies shall provide a 24-Vdc linear supply at not less than 2 SECTION 15901 Page 15

Case 1:05-cv-01121-EJD
FY 2001 MCON PROJECT

Document 13-5

Filed 05/31/2006

Page 23 of 129
12003035

P-189, BUILDING 245 EXTENSION NPS, MONTEREY, CALIFORNIA

amperes, with regulation to 0.05 percent of output voltage. Power supplies shall have a fused input, and shall be protected from voltage surges and power-line transients. Power supply output shall be protected against overvoltage and short circuits. Power supply loading shall not be greater than 1.2 amperes. 2.15.7 Transformers

UL 508 and NEMA ST 1 as applicable. Transformers, other than transformers in bridge circuits, shall have primaries wound for available voltage and secondaries wound for correct control circuit voltage. Transformers shall be sized so that connected loads equal 80 percent of rated capacity. Transformers shall be enclosed in rustproof, galvanized steel cabinets with conduit connections. Disconnect switch shall be provided on the primary side, and a fuse cutout on the secondary side. 2.15.8 Pilot Lights and Manual Switches

Device illumination shall be by light-emitting diode (LED) or neon lamp. Switches shall have operating levers and index plates showing switch positions and names of apparatus controlled or other appropriate designations. 2.16 HVAC SYSTEM CONTROL PANELS

Provide HVAC system control panels. 2.16.1 Panel Assembly

Panel shall be fabricated for bottom entry connection for control system electric power, control system main air source, control system wiring, pneumatic tubing, interconnection of control systems, interconnection of starters, and external shutdown devices. Panel shall have an operating temperature rise of not greater than 20 degrees F above an ambient temperature of 100 degrees F. 2.16.2 Panel Electrical Requirements

Control panel shall be powered by nominal 120 Vac terminating at panel on terminal blocks. Instrument cases shall be grounded. Interior and exterior panel enclosures shall be grounded. 2.16.3 Enclosures

Enclosures for each panel shall be a single door, wall-mounted box conforming to NEMA 250 with a continuous hinged and gasketed exterior door with a print pocket, key lock, and interior back panel. Inside finish shall be white enamel, and outside finish shall be gray primer over phosphatized surfaces. 2.16.4 Mounting and Labeling

Provide pilot lights, switches, panel-mounted control devices, and pressure gages shall be mounted on the door. Power conditioners, fuses, and duplex outlets shall be mounted on the interior of the cabinet. Other components housed in the panel shall be mounted on the interior back panel surface of the enclosure and shall be identified by plastic or metal nameplates which are mechanically attached to the panel. Lettering shall be cut or stamped into the nameplate to a depth of not less than 1/64 inch, and shall have SECTION 15901 Page 16

Case 1:05-cv-01121-EJD
FY 2001 MCON PROJECT

Document 13-5

Filed 05/31/2006

Page 24 of 129
12003035

P-189, BUILDING 245 EXTENSION NPS, MONTEREY, CALIFORNIA

contrasting color, produced by filling with enamel or lacquer or by use of laminated material. Painting of lettering directly on the surface of the door or interior back panel is not permitted. 2.16.5 a. Wiring and Tubing Pneumatic device inputs and outputs shall be piped to bulkhead fittings in the bottom of the panel with a 2 inch loop to facilitate replacement. Electric, electronic, and electropneumatic device signals entering and leaving the panel shall be wired to identified terminal blocks. Wiring shall be installed in wiring ducts so that devices can be added or replaced without disturbing existing wiring that is not affected by the change. Wiring to single-loop controllers shall have a 4 inch wiring loop in the horizontal wiring duct at each wiring connection. There shall be no wiring splices within the control panel. Interconnections required for power or signals shall be made on device terminals, if available, or panel terminal blocks, with not more than two wires connected to each terminal. Instrument signal grounds at the same reference level shall end at a grounding terminal connected to a common ground point for that level. Wiring shield grounds at the same reference level shall end at a grounding terminal connected to a common ground point for that level. Grounding terminal blocks shall be identified by reference level. Wiring connected to controllers shall be identified by function and polarity, e.g., process variable input and remote setpoint input and output.

b.

c.

d.

2.17

ELECTRONIC VARIABLE AIR VOLUME VAV TERMINAL UNIT CONTROLS

Provide electronic VAV terminal unit controls. 2.17.1 VAV Terminal Units

VAV terminal units shall be as specified in Section 15720, "Air Handling Units". 2.17.2 a. Terminal Unit Controls UL 916 and FCC Part 15. Controls for pressure independent boxes shall consist of a velocity sensing device in the primary air entering box, a room temperature sensing element, a damper actuator, and an adjustable microprocessor-based VAV box controller. Controls shall operate a damper for cooling and a duct coil for heating. Actuator shall open or close the device to which it is applied within 6 minutes. Controls for pressure independent boxes with recirculating fans shall consist of a velocity sensing device in the primary air entering the box, a room temperature sensing element, an adjustable microprocessor-based VAV box controller, a damper with actuator, and a duct pressure switch to operate the recirculation fan. Controller shall operate the damper for cooling and duct coil for heating.

b.

SECTION 15901

Page 17

Case 1:05-cv-01121-EJD
FY 2001 MCON PROJECT

Document 13-5

Filed 05/31/2006

Page 25 of 129
12003035

P-189, BUILDING 245 EXTENSION NPS, MONTEREY, CALIFORNIA

c.

One hand-held communication and programming device with an instruction manual, plus one additional hand-held communication device and instruction manual per 100 terminal units, shall be provided. Communication and programming device shall connect directly to the controller or to a jack at the room temperature sensing element location. Communication and programming device shall be used to read and set minimum velocity, maximum velocity, heating setpoint, and cooling setpoint, and to read air velocity and space temperature.

2.18

WIRING a. Terminal blocks shall be insulated, modular, feed-through, clamp style with recessed captive screw-type clamping mechanisms. Terminal blocks shall be rail mounted, and shall have end plates, partition plates or enclosed sides for separation. Control wiring for 24-V circuits shall be 18 AWG minimum and shall be rated for 300-V service. Wiring for circuits operating at more than 100 V shall be 14 AWG minimum and shall be rated for 600-V service. Analog signal wiring circuits within control panels shall not be less than 20 AWG and shall be rated for 300-V service. Instrumentation cable shall be 18 AWG, stranded copper, single or multiple twisted, minimum 2-inch lay of twist, 100 percent shielded pairs, and shall have 300-V insulation. Each pair shall have a 20-AWG tinned copper drain wire, individual pair, and overall insulation. Cables shall have an overall aluminum polyester or tinned overall copper cable shield tape, 20-AWG tinned-copper cable drain wire, and overall cable insulation. Nonconducting wiring ducts in control panels shall have slotted side snap-on covers, fittings for connecting ducts, mounting clips for securing ducts, and wire retaining clips. EXECUTION INSTALLATION

b.

c.

d.

e.

f.

PART 3 3.1

Perform installation under the supervision of competent technicians regularly employed in the installation of control systems. Provide components for a complete and operational control system. Provide control system complete and ready for operation, as specified and indicated. Provide dielectric isolation where dissimilar metals are used for connection and support. Penetrations through and mounting holes in the building exterior shall be watertight. Control system installation shall provide adequate clearance for control system maintenance by maintaining access spaces between coils, to mixed-air plenums, and as required to calibrate, remove, repair, or replace control system devices. Control system installation shall not interfere with the clearance requirements for mechanical and electrical system maintenance. Install devices mounted in or on piping or ductwork, on building surfaces, in mechanical and electrical spaces, or in occupied space ceilings in accordance with manufacturer's recommendations and as indicated on contract documents. Provide control devices to be installed in piping and ductwork with required gaskets, flanges, thermal compounds, insulation, piping, fittings, SECTION 15901 Page 18

Case 1:05-cv-01121-EJD
FY 2001 MCON PROJECT

Document 13-5

Filed 05/31/2006

Page 26 of 129
12003035

P-189, BUILDING 245 EXTENSION NPS, MONTEREY, CALIFORNIA

and manual valves for shutoff, equalization, purging, and calibration. Certify that installation of control system is complete and technical requirements of this section have been met. 3.1.1 Sensors

Provide sensors in locations to sense the appropriate condition. Install sensor and transmitter where easily accessible and serviceable without special tools. Sensors shall be calibrated to the accuracy specified in the contract, and operate correctly when installed. Do not install sensors designed for one application in the place of another application (e.g., replacing a duct sensor with a room sensor). 3.1.1.1 Room Sensors

Provide on interior walls to sense average room conditions. Avoid locations which may be covered by office furniture. Do not mount room sensors on exterior walls if other locations are available. Mount centerline of sensor 5 feet above finished floor. 3.1.1.2 Duct Temperature Sensors

Provide sensors in ductwork in general locations as indicated. Select specific sensor